Static Leach Analysis

Detailed extractable analysis is conducted on piping samples after seven-day static leach utilizing 18.2 megohm ultra-pure water at ambient temperature. Static leach of large pipe samples (120-square-inch wet surface area) is representative of a piping system “off-line” for an extended period of time. Under these conditions the effects of UPW can be extremely aggressive, severely affecting the amount of leachable contaminants present within the piping material.

Pipe Material
Element DL (Detection Limit) ppb Harvel LXT® High Purity PVDF High Purity PP Brand X Clean PVC Conv. PVC CPVC
TOC 5 59 90 94 1176 * 50
Flouride 2 * 77 * * * *
Chloride 0.25 2.33 1.0 0.66 2.45 0.84 49.54
Aluminum 0.05 0.30 2.3 0.68 0.54 3.10 1.16
Barium 0.01 0.04 0.24 0.09 0.01 0.22 0.05
Calcium 3 7 * 12 206 2787 15
Magnesium 0.02 0.81 0.66 1.0 2.15 11.15 2.17
Sodium 0.06 0.83 0.51 0.18 0.49 1.23 23.22
Tin 0.02 0.93 * * 0.15 0.51 1.19
Zinc 0.06 0.49 0.47 0.96 * 0.51 1.19
* = Below Detection Limit

All samples pre-rinsed identically with UPW prior to test.

  • Independent Laboratory Extractable Analysis (Balazs Analytical Laboratory)
  • Seven-Day Static Leach @ ambient temperature
  • 450mL 18.2 megohm ultra-pure water
  • 120-square-inch wet surface contact area
  • Based on 1" diameter pipe without solvent-cemented joint
  • Concentration units expressed as ug/L of Leachate (ppb)

Contact Harvel for additional detailed reports.